Unitronics · I/O Modules
Vision I/O Modules
IO-… expansion modules, EX-… adapters and V200-18 Snap-in I/O modules that extend the input/output capacity of Vision series controllers. Digital, analog, temperature and weight (loadcell) measurement in a single family.
Key Features
- Digital, analog, temperature (PT / NI / thermocouple) and weight (loadcell / strain gauge) measurement modules
- Connection of up to 8 modules to a single PLC with the EX-A2X local expansion adapter, galvanic isolation
- Remote I/O over CANbus with EX-RC1: multiple adapters per PLC, up to 8 modules per adapter
- Snap-in I/O modules that plug directly onto the back of V560, V570, V700, V1040 and V1210 panels
- Expansion up to 1,000 I/O on V560–V1210 models, 512 I/O on V350 and V430, and 256 I/O on V130
- The EX-RC1 adapter is supported by the Samba, Vision and UniStream series
I/O Expansion Modules
IO-… / EX-… expansion modules for the Vision series
| Model | Type | Digital Input | HSC | Analog Input | Temperature Measurement | Weight Measurement | Transistor Output | PWM / HSO | Relay Output | Analog Output | Operating Voltage |
|---|---|---|---|---|---|---|---|---|---|---|---|
| IO-DI8-TO8 | Digital | 8, pnp / npn | 1; 5 kHz, 16 bit | – | – | – | 8, pnp | – | – | – | 24 V DC |
| IO-DI8-RO4 | Digital | 8, pnp / npn | 1; 5 kHz, 16 bit | – | – | – | – | – | 4 | – | 24 V DC |
| IO-DI8-RO8 | Digital | 8, pnp / npn | 1; 5 kHz, 16 bit | – | – | – | – | – | 8 | – | 24 V DC |
| EX90-DI8-RO8 | Digital | 8, pnp / npn | 1; 5 kHz, 16 bit | – | – | – | – | – | 8 | – | 24 V DC |
| IO-DI16 | Digital | 16, pnp / npn | 1; 5 kHz, 16 bit | – | – | – | – | – | – | – | 24 V DC |
| IO-TO16 | Digital | – | – | – | – | – | 16, pnp | – | – | – | 24 V DC |
| IO-RO8 | Digital | – | – | – | – | – | – | – | 8 | – | 24 V DC |
| IO-RO16 | Digital | – | – | – | – | – | – | – | 16 | – | 24 V DC |
| IO-DI8ACH | Digital | 8, AC | – | – | – | – | – | – | – | – | 110 / 220 V |
| IO-AI4-AO2 | Analog | – | – | 4; 0-10 V, 0-20 mA / 4-20 mA, 12 bit | – | – | – | – | – | 2; ±10 V 12 bit + sign, 0-20 mA, 4-20 mA 12 bit | 24 V DC |
| IO-PT400 | Temperature | – | – | – | 4; PT 100 / NI 100 / NI 120 | – | – | – | – | – | Not applicable |
| IO-PT4K | Temperature | – | – | – | 4; PT 1000 / NI 1000 | – | – | – | – | – | Not applicable |
| IO-AO6X | Analog | – | – | – | – | – | – | – | – | 6 (isolated); 0-10 V, 0-20 mA, 4-20 mA, 12 bit | 24 V DC |
| IO-LC1 | Weight | 1, pnp | – | – | – | 1; loadcell / strain gauge | 2, pnp | – | – | – | 24 V DC |
| IO-LC3 | Weight | 1, pnp | – | – | – | 3; loadcell / strain gauge | 2, pnp | – | – | – | 24 V DC |
| IO-ATC8 | Analog / Temperature | – | – | 8; thermocouple, 0-10 V, 0-20 mA, 4-20 mA, 14 bit | Shared with the analog input channels (thermocouple) | – | – | – | – | – | Not applicable |
| IO-AI8 | Analog | – | – | 8; 0-10 V, 0-20 mA / 4-20 mA, 14 bit | – | – | – | – | – | – | Not applicable |
| IO-D16A3-RO16 | Combined | 16, pnp / npn | 2; 30 kHz, 32 bit | 3; 0-20 mA, 4-20 mA, 10 bit | – | – | – | – | 16 | – | 24 V DC |
| IO-D16A3-TO16 | Combined | 16, pnp / npn | 1; 30 kHz, 32 bit | 3; 0-20 mA, 4-20 mA, 10 bit | – | – | 15 pnp + 1 pnp / npn | 1; pnp 0.5 kHz, npn 50 kHz | – | – | 24 V DC |
| EX-D16A3-RO8 | Combined | 16, pnp / npn | 2; 30 kHz, 32 bit | 3; 0-20 mA, 4-20 mA, 10 bit | – | – | – | – | 8 | – | 24 V DC |
| EX-D16A3-TO16 | Combined | 16, pnp / npn | 1; 30 kHz, 32 bit | 3; 0-20 mA, 4-20 mA, 10 bit | – | – | 15 pnp + 1 pnp / npn | 1; pnp 0.5 kHz, npn 50 kHz | – | – | 24 V DC |
| EXF-RC15 | High-speed remote I/O | 9, pnp / npn | 3; 200 kHz, 32 bit | – | – | – | 4, npn | 4 (up to 3 PTO) | 2 | – | 24 V DC |
I/O Expansion Adapters (EX-A2X / EX-RC1)
| Model | Type | Description |
|---|---|---|
| EX-A2X | Local I/O module adapter | Galvanic isolation. Up to 8 modules can be connected to a single PLC. Supports 12 / 24 V DC. |
| EX-RC1 | Remote I/O module adapter (CANbus) | Multiple adapters can be connected to a single PLC, and up to 8 modules to each adapter. Supports 12 / 24 V DC. Supported by the Samba, Vision and UniStream series. |
Snap-in I/O Modules (V560 / V570 / V700 / V1040 / V1210)
| Model | Digital Input (isolated) | HSC / Encoder | Analog and Temperature Input | Transistor Output (isolated) | PWM / HSO | Relay Output | Analog Output | Operating Voltage |
|---|---|---|---|---|---|---|---|---|
| V200-18-E1B | 16, pnp / npn | 2; 10 kHz, 32 bit | 3; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 4, pnp / npn | 2; pnp 0.5 kHz, npn 50 kHz | 10 | – | 24 V DC |
| V200-18-E2B | 16, pnp / npn | 2; 10 kHz, 32 bit | 2; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 4, pnp / npn | 2; pnp 0.5 kHz, npn 50 kHz | 10 | 2; 0-10 V, 0-20 mA, 4-20 mA, 12 bit | 24 V DC |
| V200-18-E3XB | 18, pnp / npn | 2; 10 kHz, 32 bit | 4 (isolated); thermocouple, PT 100, 0-10 V, 0-20 mA, 4-20 mA, 14 bit | 2, pnp / npn | 2; pnp 0.5 kHz, npn 50 kHz | 15 | 4 (isolated); 0-10 V, 4-20 mA, 12 bit | 24 V DC |
| V200-18-E4XB | 18, pnp / npn | 2; 10 kHz, 32 bit | 4 (isolated); thermocouple, PT 100, 0-10 V, 0-20 mA, 4-20 mA, 14 bit | 15 pnp + 2 npn / pnp | 2; pnp 0.5 kHz, npn 50 kHz | – | 4 (isolated); 0-10 V, 4-20 mA, 12 bit | 24 V DC |
| V200-18-E5B | 18, pnp / npn | 2; 10 kHz, 32 bit | 3; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 15 pnp + 2 npn / pnp | 2; pnp 0.5 kHz, npn 50 kHz | – | – | 24 V DC |
| V200-18-E6B | 18, pnp / npn | 2; 10 kHz, 32 bit | 2; thermocouple, PT 100, 0-10 V, 0-20 mA, 4-20 mA, 14 bit + 3; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 2, pnp / npn | 2; pnp 0.5 kHz, npn 50 kHz | 15 | 2 (isolated); 0-10 V, 4-20 mA, 12 bit | 24 V DC |
| V200-18-E46B | 18, pnp / npn | 2; 10 kHz, 32 bit | 6; 0-10 V, 0-20 mA, 4-20 mA, 14 bit + 3; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 2, pnp / npn | 2; pnp 0.5 kHz, npn 100 kHz | 15 | 2 (isolated); 0-10 V, 4-20 mA, 12 bit | 24 V DC |
| V200-18-E62B | 30, pnp / npn | 2; 100 kHz, 32 bit | 2; 0-10 V, 0-20 mA, 4-20 mA, 10 bit | 28 pnp + 2 npn / pnp | 2; pnp 0.5 kHz, npn 100 kHz | – | – | 24 V DC |